Does it matter how deep I drive the probes?
No, not once a threshold value for maximum contact resistance has been met
(we are referring to test probe resistance here, not the installed ground
that is being tested). It is a common fallacy that driving the test probes
deeper will lower the readings. Imagine your readings changing as you drive
the probes; what would be the correct value? It's true that the resistance
of the ground under test does change as the test probes are moved, but the
standardized procedures deal with this and provide a means of determining
when the correct reading has been achieved. With respect to the probes,
this is not necessary. They need only make a minimum amount of contact with
the soil, the attainment of which can be recognized by merely observing
the display indicators. Once contact is achieved, the test may proceed.
And with instruments from AVO, the resistance tolerance in the test circuits
is particularly high, so that threshold contact is readily attained. So
much so that it may not be necessary to even penetrate the surface. Just
laying the probes flat and watering them down often lowers contact resistance
enough to meet the threshold tolerance.
My testing is all on concrete and macadam; how can I drive probes?
The good news is that you probably don't have to. Our models have uncommonly
high resistance tolerances in the test circuits (typically 4, 40, &
400 k for the current circuit, 75 k for the potential). Any surface contact
of a resistance less than these high thresholds is enough. Therefore, you
may only need to lay the test probes flat on the surface and establish contact
by wetting the area. Concrete conducts current fairly well and chances are
good that you'll have an acceptable test. Macadam is not as good because
of the non-conductive tar, but you may still be able to achieve enough contact.
You'll know because indicator lights on the tester warn you if the contact
threshold has not been met. If that becomes a problem, you can improve your
chances by using a contact mat instead of the provided probes. Mats are
flexible metallized conductive pads that mate with the surface contours.
They are readily available from ground materials suppliers.
I have no room to stretch out the leads; what do I do?
Try another method. This is not as cavalier an answer as it may sound. Good
samaritans have anticipated this problem long ago, and developed specialized
test procedures to meet it. Test procedures are described in IEEE Standard
No. 81 and are readily available from the general ground-testing literature.
Most procedures are generalized variations of the comprehensive Fall of
Potential Method but some have been devised as answers to specific situations
like testing in congested areas. The most-used procedure for this particular
problem is the Star-Delta Method. This is an adaptation of the two-point
method, with arithmetic built in to compensate for the uncertainties that
make more generalized two-point testing unreliable. Specifically, rather
than going straight out with potential and current leads, the test probes
are arranged in a fairly close triangle around the ground under test. A
series of two-point measurements are made between the various pairs of elements
in the array (probe to ground and probe to probe), plugged into a series
of equations, and then you have your answer. If there are problems in the
test setup, the arithmetic doesn't compute to a coherent answer and you
know to try again with a different configuration.
What safety precautions should I observe when performing a ground test?
Industry-standard safety practices are always a good idea, if for no other
reason than to condition personnel against becoming lax and wandering unprotected
from one electrical environment to another. But with current model Megger®
ground testers specifically, there are few requirements. The instruments
themselves present no potential hazard. While testers of years ago sometimes
used high currents and voltages, and some lines still do, all Megger models
have taken advantage of microprocessor sensitivities in order to limit both
voltage and current within levels safe for human operation. No more than
50 V and 10 mA are produced, except when using the DET2/2 in its high-current
mode, in which case a maximum of 50 mA are produced at low voltage. The
only possible hazard in a ground test then is from the electrical system
if the test is being performed on a ground electrode while it remains on
line. Incidentally, because of the low voltage and current, plus uncommon
frequency, the ground tester does not introduce any intrusive signal onto
the electrical system that might trip protective devices or interfere with
operation. The reverse can occur, however. The electrical system can intrude
on the tester. That is to say, if a fault condition occurs while the ground
test is being performed, the ground electrode will be brought on line by
the fault current going to earth and voltages can develop across the tester.
These can damage the instrument and threaten the operator. For personnel
safety, however, all that needs to be done is to follow standard safety
practices, such as wearing insulated electrical gloves and working on a
protective mat. To protect the instrument, fused leads can be used.
I've tested a ground and gotten a reading of 520 Ohms. Is there something
that I've done wrong?
Probably not. As long as the tester is in calibration and a standard test
procedure has been followed adequately, you can rely on the measurement.
The problem is with the ground, not with the operator. It is not at all
uncommon to discover grounds that are anything but! Because of neglect,
deterioration, drastic changes in environment, poor installation, lack of
forethought in design, or any of a number of common causes, ground electrodes
may be providing little or no protection. To seek out and correct these
bad grounds is why the test is being made in the first place. Do not be
surprised to find ground electrodes that measure in the hundreds, even thousands,
of Ohms. It is a good idea to first perform a few repeat tests so as to
confirm the bad news, and then start digging.
I have a large grid to test; how do I know what model to choose?
The size of the grid hardly matters to the tester. It does matter, however,
to the operator. The two principle effects of grid size are on lead lengths
and method chosen, rather than model of instrument. Any model can, at least
nominally, test any grid. Just because you might have an economical model,
don't become dismayed by a large grid, and assume a special instrument is
required. As long as an accepted test method is followed rigorously and
yields coherent results, the measurement is reliable. Large grids do, however,
often require long lead lengths and/or special test methods. It is more
important that the operator give thought to these considerations than to
the instrument itself. In some difficult situations, the high current available
from the DET2/2 can be of help in establishing adequate test current, but
this can be accomplished in other ways also, such as by driving deeper probes
or watering the probe area. A good operator relies on his own experience
as well as on the instrumentation. No model is meant to serve as a substitute
for human abilities. The combination of an experienced, thoughtful operator
and a high quality instrument is always the best tool.
How do I test a counterpoise system?
Although it is notably different in design from a standard ground rod or
bed, a counterpoise system is nothing special to the ground tester. Fall
of Potential, and its derivative methods, still provide the means of testing.
Theoretically, the system should test essentially the same from any point,
although local realities can sometimes superimpose their effects. For that
reason, it is a good idea to repeat the test in various directions, in order
to average out possible localized variations. Contact can be made with the
counterpoise system at any convenient, accessible point. Remember, as long
as the system was designed and installed correctly, all of its elements
should be in parallel with respect to the ground.
Other requirements may prevail as well with respect to the conductors coming
off the tower and their connections to the system. Therefore, it is recommended
to thoroughly examine specifications. The test may not actually entail a
single measurement, but rather it may include both the electrical relationship
of the buried system to the soil and of the conductors to the system and
the tower. The actual ground resistance measurement remains the same but
it may have to be supplemented by verification of complete continuity from
the tower to the buried electrode. Of course, this is true of any ground
but is often more elaborately and rigorously specified for counterpoise
systems because of their demanding requirements for symmetry in order to
smoothly conduct high-current faults from lightning strokes. To be thorough,
a high-current, low-resistance ohmmeter, such as a Biddle® DLRO®,
should be used to check for continuity across bonds, welds, clamps, and
similar conductive elements. But as a mere backup or spot check, multimeters,
or even a ground tester placed in two-terminal configuration, may suffice.
If the system has already been buried, there is a problem, but it is not
hopeless. An instrument such as the Multi-Amp® Safety Ground Test Set
is a highly specialized unit that can inject a high current into a buried
system in order to test that the individual elements comprising it have
sufficient continuity through bonds and welds. Do not confuse this with
a ground test, however. The electrical relationship with the surrounding
soil is separate and must be verified by a recognized ground test.
Can I test my ground conductors with your model?
Yes and no. First, it is essential to identify terms and what all is actually
required of a test procedure. It is not uncommon that what someone means
by a ground test is actually comprised of two separate measurements, one
involving the surrounding soil; the other the continuity of conductors.
Read your test specifications and requirements carefully so that nothing
is overlooked. Once installed, the ground electrode will be connected to
the electrical system by one or more conductors. This connection may vary
anywhere from the usual copper conductor extending from the ground buss
at the service entrance to a rod driven at the base of the building, to
the elaborate and symmetrical connections designed to conduct lightning
with a minimum of impedance from a tower to a counterpoise ground. These
connections must offer little resistance, otherwise the whole purpose of
establishing a ground is defeated. To thoroughly test them, an appropriate
instrument is an ohmmeter with a high test current capable of exploiting
weaknesses, loose connections, corrosion, poor welds, and such, and revealing
them in the measurement. A common multimeter does not do this, because it
makes its measurement with only a few milliamps of current. A Biddle®
DLRO®, which can output 10, or up to 100, Amps will perform a rigorous
test that will satisfy the most demanding inspector. As a handy backup check,
a multimeter can be used and even a ground tester, with its pairs of current
and potential terminals jumpered together to produce two terminals, can
serve this purpose. Mainly, just be aware that your test requirements may
include both a separate ground test and a continuity test across the connectors.
Incidentally, the ground test should be conducted before connection is made
to the electrical system. If made after, the entire power grid becomes part
of the measurement, all the way back to the substation ground. This is still
useful in determining the overall ground but the actual quality of the local
ground cannot be assessed.
I need greater lead lengths than your kit provides; what do I do?
This is simpler than it may look. There is nothing exotic about the leads
and probes used to adequately conduct a ground test. The wire is 14-gauge
braided copper, covered by rubber insulation. Any suitable wire can be used
to extend the length of the test setup, down to 18 gauge. Connection is
made to the tester by universal terminals that will accept spade lugs, banana
plugs, and even bare conductor. The probe end is a copper alligator clip
covered with a protective rubber boot. All of these materials are readily
available and can be used to increase the expanse of a test setup. Contact
resistance from stringing lengths together will most likely not present
as much of a problem as might be expected, because of the high resistance
tolerance in the test circuits. If too much contact resistance does occur,
warning lights on the tester will give the operator ample indication that
some additional steps must be taken. The probes too are not highly specialized
and general ground rods, even railroad spikes, can be used to penetrate
the soil. Again, the warning indicators will let the operator know if there
is any problem with the choice of accessory materials. It is for this reason
that AVO offers leads and probes as optional accessories, to allow planners
the option of making use of their own materials.
It has just rained heavily; will this influence my test?
Yes. There's little you can do about the weather, except be aware of its
effects and work accordingly. Soil conductivity is based on electrical conductance
by dissolved ions in moisture, not unlike the action of a car battery. When
it rains, the increased moisture dissolves salts in the soil and promotes
added conductivity. Resistance goes down. If the only goal was to "make
spec", you could try watering the area before the arrival of the inspector.
But that only defeats the purpose of installing a ground. Remember, the
electrode is only as good as its worst day, because a fault situation can
occur at any time. If it has rained all night, and the electrode barely
meets spec, chances are that it will not when tested during dry weather.
The ground design should be improved. Take all of this into consideration,
and plan accordingly.
I have a ground installed in sandy (or rocky) soil; what can I do to
test this?
The test is the same, but chances are the results won't be pleasant. It
is much more difficult to ground in sandy or rocky soil. Sand does not hold
water well and so the moisture that is needed to promote electrical conductivity
readily drains away. Rocky soils have poor overall consistency, lots of
space between individual elements, and reduced surface contact with the
buried electrode. All of these conditions mean that the original design
and installation must be more rigorous and thorough than in more agreeable
types of soil. If this wasn't done in the first place, chances are that
the results of a later ground test will prove unpleasant.
The test itself isn't categorically different, but it may be advisable to
take some special steps to make it more successful. In rocky terrain, it
may be necessary to use longer, more robust test probes in order to attain
sufficient contact with the soil. The tester's indicators will apprise the
operator of this. And since ground systems in poor soils generally have
to be larger and more elaborate, their electrical field zones are much larger
and more diffuse than those of simpler grounds. Therefore, it may require
excessive lead lengths to get outside the ground's sphere of influence for
a good test. Be prepared to switch to an alternate method that does not
require as much distance (e.g., Slope Method). In general, it is a good
practical idea to become familiar with several recognized test procedures,
some standard and some specialized, so as to be always ready to adapt to
an atypical situation if your usual method fails to provide a coherent result.
If I water the test probes to improve contact, won't this influence my
result?
No. Remember, it is the resistance of the ground electrode that is being
measured, not that of the test probe. The probe is merely a tool. Once a
minimum amount of contact is made with the soil (below a resistance threshold,
which is indicated by an LED on the tester), the setup is ready to go on
with the test. In order to achieve sufficient contact, it is perfectly legitimate
to water the area around the probes. This is like sanding an alligator clip
with emery paper before connecting to a circuit; just a specialized means
of improving contact. Watering the area around the ground electrode lower
its resistance too, and this, of course, does influence the test result.
If the test setup has adequate spacing, however, the probes will be far
enough away outside of the electrical field of the test ground so that watering
them has no influence on the test result.
Ground Testing FAQs
Category: Applications
Page