USER'S GUIDE
"ChamberMate"
Bidirectional Temperature Limit Controller


ChamberMate Photo

Third Edition
January 1, 1994


Download Instruction Book in MS-Word 97 format

TABLE OF CONTENTS
PURPOSE
DESCRIPTION
INSTALLATION & WIRING
SELECTION OF OPTIONAL OPERATING MODES
OPERATION

CIRCUIT ANALYSIS

Measuring Circuit
Linearizer Circuit
Scaling Circuit
DVM Circuit
Display Mode Selector Circuitry
Alarm Circuitry
Power Supply Circuits
Output Circuits

CALIBRATION PROCEDURE

REPLACEMENT PARTS LISTS

ChamberMate Assy
Analog PCB Assy
Digital PCB Assy
Control PCB Assy
DVM PCB ASSY
Relay Output PCB Assy



PURPOSE

This device is designed as a precision hi/lo temperature limit switch for environmental and reliability test chambers. Whenever the measured temperature strays above or below a preset "normal" range, a "high" or "low" relay contact switches to the "off" state to disable either the heating system or the cooling system. Visual LIMIT indications and an audible warning signal are provided, and the output is held off until manually reset by the user (automatic reset is a user-selected option).

An "auxiliary" contact is also provided. This third contact may be slaved to the "high" and "low" outputs (switching off when either limit is exceeded) to control power to live loads, or it may be configured to pulse remote alarm devices.


DESCRIPTION

This device is packaged as a single, panel-mounted component, consisting of printed circuit assemblies housed in a painted and anodized aluminum case. Front panel controls and indicators include :

The controller is designed for use with ISA type T (coppgr vs constantan) thermocouples, with a measuring range of -125F to +375F. Electronic cold junction compensation is provided, and the input is unaffected by sensor leadwire resistance. In the event of an open sensor circuit, the controller will produce a blank display, and a flashing SENSOR warning. A special failsafe circuit also disables both the heating and cooling outputs, assuring that both systems will remain inoperative until protection is restored. The indicating accuracy of the controller is .25%. The switching accuracy is mainly a function of its setability; about 1%.

The outputs of the controller consist of three mechanical 1P2T relay contacts, rated 10-amps at 250vac maximum. These relays are energized during all periods of normal operation, and drop out whenever a limit is exceeded, or when power is removed from the equipment.

Input power requirements are 3.5VA max at 110/120vac or 208/240vac, 50/60 Hz. All connections are made at terminal blocks on the back of the unit.



INSTALLATION & WIRING

Install the controller at a location which is convenient to system wiring, reasonably free of vibration and temperature extremes, and accessible to equipment operators. The controller is normally panel-mounted in a 3-11/16" x 8-3/16" cutout, using special mounting clamps (p/n 352052). As shown on Drawing No. 470684, the controller normally protrudes 7-3/16" behind the face of the mounting panel.

Connect an ISA type T thermocouple to the SENSOR terminal block in the upper right-hand corner of the controller, observing the RED (-) and BLU (+) color code. Use only type "XT" (copper vs constantan) thermocouple extension wire between the sensor and this terminal block. The controller is not affected by leadwire resistances less than 1000-ohms.

Connect the input power to the terminal block in the lower right-hand corner, as follows:

110/120vac circuits
208/240vac circuits
Line to terminals 1 & 2
Com to terminals 3 & 4
Ground to terminal 5
("GND")
L1 to terminal 1
jumper to terminals 2 & 3
L2 to terminal 4
Ground to terminal 5
("GND")

An indicator LED is provided on the back of the unit adjacent to each output relay. These lights will be on whenever their associated relay is energized. The relays are energized during all periods of normal operation (exception for K3 noted below), opening when limits are exceeded, or when power is removed from the unit. Whenever these relays are energized, their normally open contact set will connect COM to NORM at their associated terminal block.

The output connections are marked HIGH/COM/NORM, LOW/COM/NORM and ALARM/COM/NORM. During normal operation, COM will be connected to NORM. When a high or low limit is exceeded, COM switches to HIGH or LOW, as the case may be. Control power for the heating and cooling systems will therefore normally be wired through the COM and NORM terminals.

The operation of the auxiliary "ALARM" contact varies with the mode selected. In the slaved mode, COM will be connected to NORM until either limit is tripped, at which time COM switches to ALARM. Control power to live loads will therefore normally be wired through the COM and NORM terminals. In the alarm mode, this relay is normally off (COM to ALARM), and is pulsed on (COM to NORM) and off whenever a limit has been exceeded and the SILENCE button on the front of the unit has not been pressed (problem having not been attended to). Power to remote alarm devices will therefore also normally be wired through the COM and NORM terminals.


SELECTION OF OPTIONAL OPERATING MODES

Jumpers on the back of the unit permit the user to configure the operating mode of the unit. Two of these jumpers provide for the selection of either manual or automatic reset operation on the "High" and "Low" limit channels. If the controller is used in the manual reset mode, it will normally start-up in the "tripped" condition. A third jumper therefore provides for the selection of automatic reset on power-up, when desired. If the alarms should trip on power failures, but not in connection with routine on-off switching, connect the instrument to the main power buss, just ahead to the equipment's on/off switch, and set the third jumper at the "normal" position.)

The third "Auxiliary" contact may be slaved to the "High Limit" and "Low Limit" outputs, switching off when either limit is tripped. Or the "Aux" output may be set to pulse on and off when either limit is tripped, to operate remote alarm devices. Set the "AUX" jumper to provide the desired alternative.

Finally, a fifth jumper provides for the selection of either the Celsius or Fahrenheit indicator temperature range.

These jumpers and the above options are also illustrated on Dwg No 470684. As shipped from the factory, these jumpers are set to provide manual reset, manual power-up reset, alarm operation of the auxiliary contact, and Fahrenheit temperature indications.


OPERATION

The limit temperatures can be set by pressing either the HIGH LIMIT or LOW LIMIT reset button, then turning the respective set point adjustment as necessary to provide the desired indication.

When power is first applied, the controller will start-up in the "LIMIT" mode. Its red HIGH LIMIT and green LOW LIMIT indicators will flash on and off, and the audible alarm will sound. To start the equipment, press both RESET buttons. If the measured temperature is within the set limits, the indicators and audible alarm will be switched off, and the outputs will be enabled (units set for automatic reset will start up automatically).

If desired, automatic power-up reset operation may be selected via a jumper on the back of the unit. When this feature is used, the limit indicators will flash on momentarily when power is first applied, and will then automatically assume the normal reset condition.

During all periods of normal operation, the alarm indicators and the audible warning device will remain off, and the system will be enabled by the controller's output contacts. If the measured temperature ever exceeds a limit setting, the controller will immediately switch to the LIMIT mode. The flashing red or green indicator will then be enabled, the audible warning will sound, and the associated output will be disabled. When the temperature has returned to an acceptable level, press the lighted reset button to return to normal operation. In the meantime, the audible warning signal (and remote alarm devices, if used) can be turned off by pressing the SILENCE button.

Independent automatic reset operation is available for both the HIGH and LOW channels, via jumpers on the back of the unit. When used, the alarms will return to the normal status as soon as the measured temperature returns to within limits. Note that the selection of automatic reset inherently provides power-up reset for that channel. It is not possible to set the jumpers to provide automatic reset on both limit channels, with manual reset on power-up.


CIRCUIT ANALYSIS

Please refer to schematic diagram, Drawing No 470665. Excerpts from that diagram are provided in the following text. The full diagram is available for download (499KB) as two overlapping diagrams which may be printed on 8.5" x 11" paper using ordinary printers and commonly available graphics shareware such as LViewPro or Graphics Workshop.

You may also view the full schematic diagram immediately by opening its left half (231KB) and its right half (243KB) in your browser windows. Most browsers will add these files to their cache, and you should then be able to retrieve them from that folder and save them for future reference, if desired.

Layout diagrams for each printed circuit board are provided in the Parts List section, which appears below.


Measuring Circuit

The controller's temperature measuring circuit, the first half of U8 and its associated circuitry, converts the low level thermocouple input to a scaled and compensated high level analog voltage. The sensor, "mj" (measuring junction) is connected to U8-11, the input of this amplifier. C17 provides low pass filtering for this input. Standard units are designed to measure temperatures over the range of -125F to +375F, using a type T (copper vs constantan) thermocouple. Over this temperature range, this sensor produces emf's ranging from -3.006mV to +8.787mV. This input is amplified and scaled to provide a 0v to -5.0v analog output at U8-6. To achieve this, the gain of the amplifier is set by R17, R18 and R19 at 424.

This non-inverting amplifier will always settle at the point where the potential at its inverting input, U8-10, is exactly equal to its input, U8-11. This condition is established by a feedback current, passed from the output, U8-6, through R18 and R17 to the amplifier's inverting input. For a given input, the magnitude of the feedback current required to establish this balance is a function of R19. Having established that, the magnitude of the amplifier's output voltage then becomes a function of the feedback resistors, R17 and R18. The resistor values used permit the gain to be set exactly at 423.98, with a calibration range of about 2% to accommodate all tolerances.

Thermocouple circuits necessarily involve a second junction, sometimes called the "reference junction". This junction, shown as "rj" on the schematic, has the same "emf vs temperature" characteristic as the sensor. It occurs in series with the sensor's emf, with the opposite polarity. The emf produced by the "rj" junction is algebraically summed with the sensor emf, so any variation of the ambient temperature directly affects the measurement.

U5, R20 and R21 provide reference junction compensation, which minimizes errors due to variations in ambient temperature. U5, which is located at the (-) end of the SENSOR terminal block, is an integrated circuit temperature sensor, which produces an output proportional to its absolute temperature. This output varies 10mV/C, and is scaled by R21 to produce a feedback current through R17 and R18 which will be approximately equal and opposite to that being caused by the influence of the reference junction emf. At room temperature, the emf produced at rj varies about 40.7uV/C which, in turn, produces a feedback current of about 40.7nA through R21. A 1C ambient temperature change will also result in a 10mV variation at U5. This will produce a -41nA change in the total feedback current, which approximately cancels out the shift produced by rj.

U4, R14, R15 Rzt and R16 provide a means of shifting the amplifier's output to zero with a -125F input at "mj". U4 is a precision voltage reference integrated circuit, which provides a stable +6.9v at its junction with R14 and R15. At -125F, the mj input will be -3.006mV. Assuming a 25C ambient temperature, the emf produced by rj will be about +0.992mV, so the net input will be about +3.998mV, producing an offset of about +1.7 volts at U8-6.

Meanwhile, the voltage at the U5, R20 node varies with absolute temperature by 10mV/K, and will therefore be about +2.98v (0C = 273K). This produces a compensator-related offset at U8-6 of about -5.2 volts.

U8 is a precision op amp, with negligible offsets, so the total value of the offsets is therefore about -3.5 volts. To shift the output level back to zero, R16 is adjusted so that the zero network injects a current into the feedback node which is about equal and opposite to that caused by the total offsets; about -3.5v/422.98K = -8.3uA. Rzt is a "zero trim" adjustment, and is located on the back of the unit next to the sensor input terminals.


Linearizer Circuit

The "emf vs temperature" response of the thermocouple temperature sensor is highly nonlinear, varying from 16.6uV/F at -125F to 29.2uV/F at +375F. To provide a highly accurate digital temperature read-out, U8 and U9 convert the nonlinear 0/-5.00v measuring circuit output (U8-6) to a linear analog at U8-13. The linear analog has a range of 0/+5.00v (slope = 10mV/F).

A "piecewise" linearizing strategy is used, which breaks down the output at U8-6 into five segments. The apparent gain of the inverting buffer, U8's second half, is readjusted as necessary to produce a linear 10mV/deg slope within each segment. For example, the non-inverting input at U9-5 is held at +3.752 volts by the voltage divider R31 - R35. With the R24/R25 node at any higher level, U9-7, and all the other outputs of U9, will be at the negative saturation limit. Because of the diodes CR9 thru CR12, U9 makes no contribution to the output under these circumstances.

As the temperature decreases, the R24/R25 node drops below the +3.752 volt threshold (U8-13 = +3.843v), U9-7 swings to +3.752 volts plus the diode drop, acting like a dc buffer which holds U9-6 at +3.752 volts as the voltage at U8-13 continues to decrease. This produces a small current in R27. Since the other three linearizer stages are still off, this current is provided from the output U8-13, through R25. In order to provide this additional current, U8-13 drops to a slightly less positive level than would otherwise be required to satisfy the normal R23 feedback requirement.

As the temperature continues to fall, the voltage at the R24/R25 node decreases. This increases the linearizer current, which increases the resulting offset factor in the U8-13 output. When the R24/R25 node falls to +2.757 volts, the next linearizer stage is enabled, increasing the rate of curve correction. By increasing the slope-compensating action as the measured temperature decreases, the linearizer converts the sensor's "curve" to a constant 10mV/F slope.

Without linearization, measuring errors as large as 33.3F could result. The theoretical maximum error of this linearization scheme is -1.7F occurring at -76F.



Scaling Circuit

The indicator A/D converter is basically a digital millivolt meter. The 0/+5.00v output provided at U8-13, and the limit set point analog voltages from R67 and R68, must therefore be converted to -125mV/+375mV to provide a "-125F" to "+375F" display. The scaling circuit also converts these analog voltages to equivalent "C" values.

Analog switch U10 multiplexes the analogs into buffer input U11-3. The output of this buffer is connected to two voltage dividers. The R36 - R38 divider converts the 5-volt analog to a 0/500mV analog, representing the 500F span. The R39 - R41 divider converts the 5-volt analog to a 0/278mV analog, representing the equivalent 278C span. Either the "F" or the "C" analog is selected by U12, is buffered, then applied to R42, an input to a unity gain inverter. The inverted output, U11-8, is then applied to R44, one input of a unity gain summing circuit.

At this circuit, the analog is summed with an offsetting voltage selected by two additional sections of U12. In the "F" display mode, R48 and R49 injects +12.5uA into the feedback node, which shifts the output at U11-14 in the negative direction by exactly 125mV. This provides a "-125" read-out when the measuring circuit analog is at zero volts. In the "C" display mode, an offsetting current of +8.72uA is provided by R50 and R51, to provide -87.2mV at U11-14 (-125F = -87.2C).

The "display blank" input to R46 is taken from the CR15/CR16 junction at U18, and is normally open since the diodes are normally reverse biased. Certain sensor faults cause U18 to forward bias one of these diodes, imposing a -13.3v potential on R46. This forces U11-14 to at least +2.5v, which activates the over-range function of the A/D converter, producing a blank display.



DVM Circuit

The scaled and level-shifted analog voltage at U11-14 is applied to the input of DVM circuit, U14, through low pass filter R52 and C31. U14 is a dual-slope 3-1/2 digit A/D converter which provides 7-segment outputs to operate the digital display system. The most significant digit is not used in this application, and zero-blanking is not provided.

U14 does the A/D conversion in three phases. First, the converter is internally zeroed. Next, the input voltage is applied to an integrator, the output of which increases from zero at a linear rate until stopped at the end of this precisely timed period. Since the integrator's output slope is a function of its input voltage, its output at the end of this (integrate) phase is directly proportional to the input voltage. In the third and final (de-integrate) phase, the precision +1.000v reference voltage is applied to the integrator to drive its output back to zero at a known rate, while a counter system measures the time required to do so. The resulting count is therefore proportional to the magnitude of the input voltage, and is converted from binary to 7-segment code for display purposes.

Peripheral circuitry includes U15, which provides a +1.000v reference voltage, and U16, which provides a -5v supply for the DVM chip. The DVM chip handles all other necessary

functions internally. A jumper on the back of the unit permits the selection of either a"F" or "C" character for display purposes. Two gates of U26 buffer the choice to analog switch U12 in the scaling circuitry.


Display Mode Selector Circuitry

The digital display system is used to read-out the high and low limit set points as well as the measured temperature value, and can display all values in either F or C. The display mode is selected by the circuitry composed of U26 and U27.

When the high limit reset button is pressed, U26-8 goes high and enables U10-3 to connect the high limit analog to the scaling circuit at U11-3. At the same time, U27-11 is forced low, which disconnects the measuring circuit analog from U11-3. The low limit setting is selected in a similar manner. The circuit is rather straightforward, and tracing the logic is left as an exercise for the reader.



Alarm Circuitry

U18 provides a system of comparators which monitors the measured temperature with respect to high and low limit settings, and for "reasonableness". U17 provides a precision +6.9v reference for the limit set points, R67 and R68. These set point outputs provide one input to their respective comparator circuits, while the 0/+5.00v temperature analog voltage is connected to the other inputs. When the analog voltage is less than the high limit set point, and greater than the low limit set point, both U18-14 and U18-8 will be low. U19-3 and U19-4 will therefore be high.

Furthermore, when the analog voltage is greater than -50mV, but less than +5.07v, failsafe detector outputs U18-1 and U18-7 will both be high, and U19-10 will therefore be low.

Pressing both reset buttons, S1 and S2, forces U20-3 and U20-4 high. With all three inputs high, U21-6 and U21-9 go low. This disables both the high limit and low limit indicators, enables the output transistors, Q2 and Q4,and latches U20-3 and U20-4 at the high level. With both of its inputs high, U24-4 will be low, which turns off Q7 and DS-8 and turns on Q9 (in the "slave" mode). This is the normal operating status.

If the measured temperature strays outside of the set range, either the high limit or low limit will be tripped, and the above status for that limit will be reversed; the indicator will be on and output transistor off. The indicators are gated by a flasher signal provided from U23-3.

When neither limit is tripped, U24-4 will be low. U23-4 and U22-8 will therefore both be low, holding both the audible warning device (beeper) and the "SILENCED" indicator off. When either one(or both) of the limits are tripped, U24-4 goes high. This enables the audible warning device, but not the "SILENCED" indicator. Pressing S3 forces U24-10 high. U24-11 then goes low, which latches the beeper off, and the "SILENCED" indicator on. Both the beeper and the "SILENCED" indicator are also modulated by the flasher signal.

At power-on, U18-7 is initially held low as C41 begins to charge. This trips both limits and toggles the sensor fault indicator. A momentary loss of power will therefore trip both limits. An open sensor connection will cause the measuring circuit to provide abnormal analog voltage levels and toggle either U18-1 or U18-7. A flashing "SENSOR" warning signal via U22-6, and both limits will also be tripped. U24-3, Q5 and Q6 comprise a power-up reset timer.



Power Supply Circuits

Power for the controller can be taken from either 110/120vac or 208/240vac, 50/60 Hz lines. The controller circuitry uses +15v, -15v and +5.1v dc voltages. The +/-15v levels are provided by T2 and its associated bilateral full-wave rectifier circuit. Regulators U2 and U3 stabilize these supply voltages at the required +15v and -15v levels. A separate +5.1v supply is provided for the controller's logic and display circuitry by T1 and regulator U1. All three of these supplies are adjustable, and are set precisely at the 15v and 5.1v levels. The 15v potentials are re-stabilized at +/-12v for use at the low level measuring circuit, U8.


Output Circuitry

Separate 1P2T contacts capable of switching 10-amps ant 250vac are provided for each of the three outputs. A LED indicator is provided near, and operates with, each relay. The relays are de-energized by abnormal operating conditions (COM to HIGH or COM to LOW and COM to ALARM).


CALIBRATION PROCEDURE

Please refer to analog circuit board layout Drawing No. 470668 and perform the following adjustments.

NOTE: allow at least 10-minutes after applying power for circuit temperatures to stabilize prior to final calibration.

1. Connect a digital voltmeter between the right-hand pin of U3, and ground ([-] side of C13, C14 or C15). Adjust the "-15v" trimmer, R13, for an indication of exactly -15.0v.

2. Connect the DVM (+) lead to the center pin of U2. Adjust the "+15v" trimmer, R10, to provide an indication of exactly +15.0v

3. Connect the (+) lead to U12-14. Adjust the "+5.1v" trimmer on the bottom board (accessible through the hole in the top board) to provide an indication of exactly +5.1v

4. Trip the limits to provide an audible warning. Adjust the "tone" trimmer, R85 on the bottom board (accessible through the hole in the top board) to find the peak audible output.

5. Connect the (+) lead to the wire loop by the trimmer on the DVM board. Adjust "Vref" trimmer, R54, to provide an indication of exactly +1.000v (see Dwg No 470671, page 24).

6. Turn the low limit all the way counterclockwise, and the high limit fully clockwise. Connect the DVM (+) lead to U11-1. Select the LOW LIMIT display mode. Adjust the "-125F" trimmer, R49, for a read-out of exactly -125F, and the "-87C" trimmer, R51, for an indication of exactly -87C.

7. Select the HIGH LIMIT display mode, then adjust the "SP Span" trimmer, R65, to provide a DVM indication of exactly +5.00v.

8. With the HIGH LIMIT still selected, adjust the "F Span" trimmer, R37, to provide a display indication of exactly 375F, then adjust the "C Span" trimmer, R40 to display 191C.

9. Disconnect the sensor, and connect a compensated portable potentiometer or precision mV source to the input terminals of the controller. Set the input at "-125F" or -3.006mV. With the DVM still connected between U11-1, and ground, center the Rzt adjustment and adjust the "Zero" trimmer, R16, to provide a DVM indication of exactly 0.00v.

10. Set the input at "+375F" or +8.787mV, and adjust the "Span" trimmer, R17, to provide an indication of exactly +5.00v. Large span adjustments will effect the zero adjustment somewhat; therefore repeat Steps 9 and 10 if a large span adjustment was required.

11. Check the limit accuracy, and the operation of the associated lights and relay contacts. Set the input at about "+300F", and slowly reduce the HIGH LIMIT setting. When the displayed setting falls just below "300", the high limit alarm should trip. Press the SILENCE button and observe that the audible warning is canceled. Reset the high limit, and check the LOW LIMIT in a similar manner.


REPLACEMENT PARTS LIST

This section of the handbook includes parts lists for each major assembly and repairable subassembly. This lists are arranged by part number, as indicated in the table of contents. Each list includes a component layout drawing, which physically located most items.

Every item used in an assembly is identified in its parts list. The various parts are listed by part number. The six-digit part numbering system has a logical order, which is summarized as follows:


Class Codes
Items Covered
000000 - 049000
   Major Assemblies & Subassemblies
050000 - 099000
   Electronic Component Parts
100000 - 139000
   Electromechanical Parts
140000 - 169000
   Optical Parts, Sensors
170000 - 199000
   Wiring & Wiring Hardware
200000 - 209000
   Printed Circuit Boards
210000 - 259000
   Electrical Parts & Hardware
260000 - 289000
   Mechanical Hardware
290000 - 329000
   Fluidic (Pneumatic) Parts & Hardware
330000 - 399000
   Mechanical & Structural Parts
400000 - up
   Drawings, Publications & Literature

Since the manufacturer's name and part number are often printed on purchased parts, this information is included in the parts lists to help you properly identify the item in question. Purchased parts are often provided by alternate sources however, so this information should be taken as representative, rather than absolute.


Part Number: 012019
Drawing Number: 470665

"ChamberMate" BI-DIRECTIONAL TEMPERATURE LIMIT CONTROLLER

PART # DESCRIPTION MFGR MFGR'S NO QTY UM
048062 ANALOG PCB ASSY, TLC-II WRNR 048062/470668
1
EA
048063 DIGITAL PCB ASSY, TLC-II WRNR 048063/470669
1
EA
048064 CONTROL PCB ASSY, TLC-II WRNR 048064/470670
1
EA
048065 DVM PCB ASSY, TLC-II WRNR 048065/470671
1
EA
048066 RELAY PCB ASSY, TLC-II WRNR 048066/470672
1
EA
142003 FILTER, RED DISPLAY 1.5"x3.0" WRNR 142003
1
EA
251018 INSULATOR, TLC-II WRNR 251018/470683
1
EA
266002 STICK MOUNT, GREEN MEIJ `
1
EA
271026 SCREW, BDR HD 6-32x.250
8
EA
271028 SCREW, BDR HD 6-32x.500
4
EA
271136 SCREW, FIL HD 10-32x1.00
2
EA
271259 SCREW, TRUS HD 6-32x.250 BLK
8
EA
272038 WASHER, NYLON PLAIN #4 REG KEYS 3358
1
EA
272041 WASHER, NYLON PLAIN #6 KEYS 3163
1
EA
279001 STANDOFF, SWAGE 6-32x.250 RAF 3047-B-632-B
9
EA
279004 STUD, CAPTIVE 4-40x.250 CFC CH-440-10-C
4
EA
279007 CAP NUT, 10-32 CFC CF74-1032
2
EA
279009 THREADED INSERT, 6-32x.063 SS CFC CLF-632-1
8
EA
279022 SPACER, M-F TYPE 6-32x1.25 EFJ J217
5
EA
279024 SPACER, M-F TYPE 6-32x.375 SMTH 8249
1
EA
279026 SPACER, MM-F TYPE 6-32x.250 KEYS 8717
1
EA
351030 BEZEL, FRT WRNR 351030/470698
1
EA
351042 CHASSIS, TLC-II WRNR 351042/470694
1
EA
352052 MOUNTING CLAMP WRNR 352052/470602
2
EA
352056 COVER PLATE, INTERNAL WRNR 352056/470694
1
EA
353026 COVER, FRT WRNR 353026/470695
1
EA




Part Number: 048062
Drawing Number:
470668

"ChamberMate" ANALOG PCB ASSY

PART # DESCRIPTION MFGR MFGR'S NO QTY UM
051049 RESISTOR, CFLM 1/4W 5% 100 DIGI 100Q
1
EA
051076 RESISTOR, CFLM 1/4W 5% 1.3K MOUS 29SJ250-1.3K
1
EA
051083 RESISTOR, CFLM 1/4W 5% 2 7K MOUS 29SJ250-2.7K
1
EA
051095 RESISTOR, CFLM 1/4W 5% 8.2K MOUS 29SJ250-8.2K
1
EA
051096 RESISTOR, CFLM 1/4W 5% 9.1K MOUS 29SJ250-9.1K
1
EA
051099 RESISTOR, CFLM 1/4W 5% 12K MOUS 29SJ250-12K
1
EA
051106 RESISTOR, CFLM 1/4W 5% 24K MOUS 29SJ250-24K
3
EA
051107 RESISTOR, CFLM 1/4W 5% 27K DIGI 27KQ
1
EA
051113 RESISTOR, CFLM 1/4W 5% 47K MOUS 29SJ250-47K
1
EA
051121 RESISTOR, CFLM 1/4W 5% 100K MOUS 29SJ250-100K
2
EA
052209 RESISTOR, MFLM 1/4W 1% 121 NIC 121X
1
EA
052237 RESISTOR, MFLM 1/4W 1% 237 NIC 237X
1
EA
052238 RESISTOR, MFLM 1/4W 1% 243 NIC 243X
1
EA
052278 RESISTOR, MFLM 1/4W 1% 634 NIC 634X
1
EA
052288 RESISTOR, MFLM 1/4W 1% 806 NIC 806X
1
EA
052295 RESISTOR, MFLM 1/4W 1% 953 NIC 953X
1
EA
052301 RESISTOR, MFLM 1/4W 1% 1.00K NIC 1.00KX
2
EA
052302 RESISTOR, MFLM 1/4W 1% 1.02K NIC 102KX
1
EA
052306 RESISTOR, MFLM 1/4W 1% 1.13K NIC 1.13KX
1
EA
052309 RESISTOR, MFLM 1/4W 1% 1.21K NIC 1.21KX
1
EA
052313 RESISTOR, MFLM 1/4W 1% 1.33K NIC 1.33KX
1
EA
052321 RESISTOR, MFLM 1/4W 1% 1.62K NIC 1.62KX
1
EA
052327 RESISTOR, MFLM 1/4W 1% 1.87K NIC 1.87KX
1
EA
052337 RESISTOR, MFLM 1/4W 1% 2.37K NIC 2.37KX
1
EA
052340 RESISTOR, MFLM 1/4W 1% 2.55K NIC 2.55KX
1
EA
052369 RESISTOR, MFLM 1/4W 1% 5.11K NIC 5.11KX
1
EA
052393 RESISTOR, MFLM 1/4W 1% 9.09K IC 9.09KX
1
EA
052396 RESISTOR, MFLM 1/4W 1% 9.76K NIC 9.76KX
1
EA
052401 RESISTOR, MFLM 1/4W 1% 10.0K NIC 10.0KX
6
EA
052406 RESISTOR, MFLM 1/4W 1% 11.3K NIC 11.3KX
1
EA
052426 RESISTOR, MFLM 1/4W 1% 18.2K NIC 18.2KX
1
EA
052528 RESISTOR, MFLM 1/4W 1% 191K NIC 191KX
1
EA
052538 RESISTOR, MFLM 1/4W 1% 243K NIC 243KX
1
EA
052543 RESISTOR, MFLM 1/4W 1% 274K NIC 274KX
1
EA
052552 RESISTOR, MFLM 1/4W 1% 340K NIC 340KX
1
EA
052554 RESISTOR, MFLM 1/4W 1% 357K NIC 357KX
1
EA
054004 POTENTIOMETER, TRIM 1T-3/8 100 PANA 0FA12
2
EA
054005 POTENTIOMETER, TRIM 1T-3/8 200 PANA 0FA22
1
EA
054006 POTENTIOMETER, TRIM 1T-3/8 500 PANA 0FA52
1
EA
054007 POTENTIOMETER, TRIM 1T-3/8 1K PANA 0FA13
1
EA
054011 POTENTIOMETER, TRIM 1T-3/8 20K PANA 0FA24
3
EA
054013 POTENTIOMETER, TRM 1T-3/8 100K PANA 0FA15
1
EA
062060 CAPACITOR, CRMC 25V .01uF NIC NCD.01M25MX5U
2
EA
063013 CAPACITOR, TANT 35V 1.0uF NEC 1.0M35
10
EA
062067 CAPACITOR, CRMC 50V 1uF NIC NCD.1M50MX5U
7
EA
063045 CAPACITOR, TANT 25V 10uF NEC 10M25
6
EA
081001 DIODE, SIG MOUS 1N4148
8
EA
081015 DIODE, SIGNAL LOW iR SPC 1N457
2
EA
091013 IC, QUAD BILATERAL SWITCH RCA CD4066BE
2
EA
093002 IC, QUAD OP AMP NS LM324N
2
EA
093010 IC, ADJ POS 1.5A REGULATOR NS LM317T
1
EA
093011 IC, +12V 100mA REGULATOR NEC UPC78L12
1
EA
093012 IC, -12V 100mA REGULATOR PANA AN79L12
1
EA
093013 IC, ADJ NEG 1.5A REGULATOR NEC UPC337H
1
EA
093016 IC, PRECISION 6.9V REFERENCE NS LM329DZ
1
EA
093017 IC, PRECISION 2.5V REFERENCE NS LM336Z-2.5
2
EA
093030 IC, DUAL PRECISION OP AMP LTEC OP227GN
1
EA
093032 IC, PRECISION QUAD OP AMP LTEC LT1014DN
1
EA
173003 HEADER, RA/SR MALE 36-W GOLD APT 929648-01-36
25
EA
175002 SOCKET, IC 14-PIN SOLDER TAIL AMP A9314
6
EA
201073 PTD CKT BOARD, TLC-II ANALOG WRNR 201073/470673
1
EA
271014 SCREW, BDR HD 4-40x.250
2
EA
273002 LOCKWASHER, HELIC #4 REG
2
EA
274002 NUT, HEX 4-40
2
EA




Part Number: 048063
Drawing Number:
470669

"ChamberMate" DIGITAL PCB ASSY

PART # DESCRIPTION MFGR MFGR'S NO QTY UM
051075 RESISTOR, CFLM 1/4W 5% 1.2K MOUS 29SJ250-1.2K
3
EA
051089 RESISTOR, CFLM 1/4W 5% 4.7K MOUS 29SJ250-4.7K
1
EA
051106 RESISTOR, CFLM 1/4W 5% 24K MOUS 29SJ250-24K
4
EA
051129 RESISTOR, CFLM 1/4W 5% 220K MOUS 29SJ250-220K
1
EA
051147 RESISTOR, CFLM 1/4W 5% 1.2MEG MOUS 29SJ250-1.2M
1
EA
052238 RESISTOR, MFLM 1/8W 1% 243 NIC 243X
1
EA
052282 RESISTOR, MFLM 1/8W 1% 698 NIC 698X
1
EA
054004 POTENTIOMETER, TRIM 1T-3/8 100 PANA 0FA12
1
EA
054008 POTENTIOMETER, TRIM 1T-3/8 2K PANA 0FA23
1
EA
056001 VARISTOR, 180mJ 31VDC PANA P7020
4
EA
062060 CAPACITOR, CRMC 25V .01uF NIC NCD.01M25MX5U
7
EA
062067 CAPACITOR, CRMC 50V .1uF NIC NCD.1M50MX5U
5
EA
063013 CAPACITOR, TANT 35V 1.0uF NEC 1.0M35
6
EA
063045 CAPACITOR, TANT 25V 10uF NEC 10M25
2
EA
064004 CAPACITOR, ELEC 35V 470uF PANA P6255
2
EA
064016 CAPACITOR, ELEC 16V 4700uF PANA P6900
1
EA
067046 CAPACITOR, FILM 100V .1uF MLRY 160104J100C
1
EA
071005 TRNSFORMER, PWR 34VCT@170MA SGNL LP34-170
1
EA
071006 TRNSFORMER, PWR 16VCT@350MA SGNL LP16-350
1
EA
081002 DIODE, RECT 200V 1A MOT 1N4002
6
EA
083021 TRANSISTOR, NPN GENL PURPOSE MOUS KN3904
5
EA
091001 IC, QUAD 2-INPUT SCHMIT NAND RCA CD4093BE
5
EA
091011 IC, TRIPLE 3-INPUT NAND GATE RCA CD4023BE
2
EA
091018 IC, QUAD 2-INPUT NAND (OC) RCA CD74HC03E
1
EA
091019 IC, HEX SCHMITT INVERTER RCA CD74HC14
1
EA
093010 IC, ADJ POS 1.5A REGULATOR NS LM317T
1
EA
173003 HEADER, RS/SR MALE 36-W GOLD APT 929648-01-36
30
EA
173006 RECEPTACLE, STR/SR PCB 36-W GD APT 929850-01-36
18
EA
175002 SOCKET, IC 14-PIN SOLDER TAIL AMP A9314
9
EA
201074 PTD CKT BOARD, TLC-II DIGITAL WRNR 470674
1
EA
271014 SCREW, BDR HD 4-40x.250
1
EA
273002 LOCKWASHER, HELIC #4 REG
1
EA
274002 NUT, HEX 4-40
1
EA




Part Number: 048064
Drawing Number:
470670

"ChamberMate" CONTROL PCB ASSY

PART # DESCRIPTION MFGR MFGR'S NO QTY UM
051059 RESISTOR, CFLM 1/4W 5% 270 MOUS 29SJ250-270
3
EA
051073 RESISTOR, CFLM 1/4W 5% 1.0K MOUS 29SJ250-1.0K
1
EA
051082 RESISTOR, CFLM 1/4W 5% 2.4K MOUS 29SJ250-2.4K
3
EA
051087 RESISTOR, CFLM 1/4W 5% 3.9K MOUS 29SJ250-3.9K
1
EA
083021 TRANSISTOR, NPN MOUS KN3904
1
EA
102010 SWITCH, PB PCB SHDW 200130
3
EA
109005 KEY CAP, GRY 1-LED SHDW 71077
3
EA
121003 LED, T1 MIN DIFF RED ROHM SLR-34 VR3
1
EA
121009 LED, T1 MIN DIFF YLW ROHM SLR-34 YY3
1
EA
121010 LED, T1 MIN DIFF GRN ROHM SLR-34 MG3
1
EA
124001 SOUND TRANSDUCER BELL MS-1
1
EA
173006 RECEPTACLE, STR/SR PCB 36-W GD 929850-01-35
10
EA
201075 PTD CKT BOARD, TLC-II CONTROL WRNR 470675
1
EA




Part Number: 048065
Drawing Number:
470671

"ChamberMate" DVM PCB ASSY

PART # DESCRIPTION MFGR MFGR'S NO QTY UM
051059 RESISTOR, CFLM 1/4W 5% 270 MOUS 29SJ250-270
1
EA
051061 RESISTOR, CFLM 1/4W 5% 330 MOUS 29SJ250-330
5
EA
051082 RESISTOR, CFLM 1/4W 5% 2.4K MOUS 29SJ250-2.4K
1
EA
051121 RESISTOR, CFLM 1/4W 5% 100K MOUS 29SJ250-100K
2
EA
051125 RESISTOR, CFLM 1/4W 5% 150K MOUS 29SJ250-150K
1
EA
052412 RESISTOR, MFLM 1/4W 5% 13.0K DIGI 13.0KX
1
EA
052439 RESISTOR, MFLM 1/4W 5% 24.9K DIGI 24.9KX
1
EA
054010 POTENTIOMETER, TRIM 1T-3/8 10K BRNS 3386P-1-103
1
EA
054042 POTENTIOMETER, CONT 1T 5K ALPH 31VC401
2
EA
062067 CAPACITOR, CRMC 50V .1uF NIC P4164-ND
1
EA
063013 CAPACITOR, TANT 35V 1.0uF NEC 1.0M35
3
EA
067046 CAPACITOR, FILM 400V .1uF THOM MC104K1C
1
EA
067050 CAPACITOR, FILM 100V .22uF THOM MC224K1D
1
EA
067054 CAPACITOR, FILM 63V .47uF THOM MC474K1F
1
EA
067087 CAPACITOR, POLY 25V 100pF PANA ECQ-P1H101JZ
1
EA
093017 IC, 2.5V REFERENCE NS LM336Z-2.5
1
EA
093026 IC, -5V 100mA REGULATOR NS LM79L05ACZ
1
EA
094002 IC, D/A DISPLAY CONVERTER TLDN TSC7107CPL
1
EA
121003 LED, T1 MIN DIFF RED ROHM SLR-34 UR3
1
EA
125003 DISPLAY, .43" DIGIT RED (CA) PANA LN514OA
4
EA
125004 DISPLAY, .30" DIGIT RED (CA) PANA LN513OA
1
EA
173003 HEADER, RA/SR MALE 36-W GOLD APT 929648-01-36
18
EA
173006 RECEPTACLE, STR/SR PCB 36-W GD APT 929850-01-36
20
EA
175017 SOCKET, IC 40-PIN SOLDER TAIL AMP A9340
1
EA
201076 PTD CKT BOARD, TLC-II DVM WRNR 470676
1
EA
274009 NUT, HEX 3/8-24 A-B w/054042
2
EA
279001 STANDOFF, SWAGE TYPE 6-32x.250 RAF 3047-B-632-B-0
2
EA
279032 STANDOFF, SWAGE TYPE 6-32x.375 KEYS 1561B
1
EA




Part Number: 048066
Drawing Number:
470734

"ChamberMate" RELAY OUTPUT PCB ASSY

PART # DESCRIPTION MFGR MFGR'S NO QTY UM
051045 RESISTOR, CFLM 1/4W 5% 68 MOUS 29SJ250-68
3
EA
054012 POTENTIOMETER, TRIM 1T-3/8 50K BRNS 3386P-1-503
1
EA
081003 DIODE, RECT 400V 1A MOT 1N4004
3
EA
093029 IC, TEMP SENSOR NS LM335Z
1
EA
111004 COVER, MIN PCB RELAY P&B 35C620
3
EA
111005 RELAY, MIN PCB 24V 1P2T P&B T90N5D1224
3
EA
121003 LED, MIN RED DIFF T1 ROHM SLR-34 VR3
3
EA
173002 SHUNT 2-W APT 929950-00
5
EA
173005 HEADER, MALE PCB STR 3-W APT 4-103321-0
5
EA
173006 RECEPTACLE, SSTR/SR PCB 36-W APT 929850-01-36
26
EA
176006 TERMINAL STRIP, PCB 3-W MOUS ME153-2103
4
EA
176007 TERMINAL STRIP, PCB 2-W MOUS ME153-2102
2
EA
201077 PTD CKT BOARD, TLC-II RELAY WRNR 470677
1
EA





FireRightControls/Warner Instruments
1320 Fulton Street Box 604
Grand Haven, Michigan 49417-0604 USA
Phone: (616) 842-7658
FAX: (616) 482-1471
e-mail: info@fireright.com

Back   Top


Page Last Revised on March 29, 1998
©Copyright Warner Instruments 1996 ~ 1998